Mobile(Whatsapp/Wechat):+8613702471397

Advantech ADAM-4019+ 8Thermocouple Modbus RS-485 Remote I/O

    8ch thermocouple(can be set to voltage or current)

    Protocols:Modbus RTU,ASCII

    Watchdog timer to recover the system

    3000VDC isolation protection

    Wiring burned-out detection function

ADAM-4019+-F
Analog Input Burn-out Detection Yes
Communications Interface RS-485
Environment Isolation Voltage 3,000 VDC
Environment Operating Temperature -10~70 °C (14~158 °F)
General Connectors 2 x 10-pin plug-in screw terminal
General Protocol ASCII command, Modbus/RTU
Power Requirements Input Voltage 10~30 VDC
Thermocouple Input Channels 8
Thermocouple Input Input Type mA, mV, V, T/C: J, K, T, E, R, S, B, N type
Thermocouple Input Resolution 16-bit
Thermocouple Input Sample Range 10 S/s (sum)
Thermocouple Input Temperature Range Type J (0~760° C), Type K (0~1370° C), Type T (-100~400° C), Type E (0~1000° C), Type R (500~1750° C), Type S (500~1750° C), Type B (500~1800° C), Type N (-200~1300° C)
Hardware Certification CE, FCC
Analog Input Input Range ±100 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V, ±10 V, 0~20mA, 4 ~ 20 mA, ±20 mA, 0~100 mV, 0~500 mV, 0~1 V, 0~2.5 V, 0~5 V, 0~10 V

Cart review